Meet the 50kVA Cat generator. The DE50 GC is Caterpillar’s answer for businesses that want a premium name in the 50kVA class. It runs a turbocharged Cat C3.3 engine at 1500rpm with a Cat brushless alternator and the GCCP 1.1 control panel, in a compact package just over 2.2 metres long.
It’s one of the most searched-for generators on our site, and it suits clinics, schools, offices, retail centres, farms and light industry with a three-phase supply.
What it will run
It’s rated at 50kVA / 40kW for standby duty, which is how most South African businesses use a generator: backup during outages. Plan around 32kW for continuous running during an outage, about 10.6kW per phase. That covers a medium office with aircons, a supermarket’s refrigeration and tills, or a farm with pumps, cold rooms and a workshop.
Fuel use
Cat publishes fuel figures at three loads, which makes budgeting easy: 6 litres an hour at 50% load, 8.7 litres at 75% and 11.7 litres at full load. The 103-litre tank gives about 12 hours at 75% load. For longer outages, an external or bunded tank can be added.
Specifications
| Model | Cat DE50 GC |
| Standby power | 50kVA / 40kW |
| Phase | Three phase, 400V, 50Hz, 0.8 power factor |
| Engine | Cat C3.3, 3 cylinder in-line, 3.3 litre, turbocharged |
| Engine speed | 1500rpm, mechanical governor |
| Alternator | Cat, brushless, 4 pole, single bearing, AVR, class H, IP23 |
| Control panel | Cat GCCP 1.1 |
| Fuel tank | 103 litres |
| Fuel use | 6.0 L/h at 50%, 8.7 L/h at 75%, 11.7 L/h at 100% load |
| Weight | 1,031kg |
| Dimensions (L x W x H) | 2278 x 900 x 1332mm |
Installation
A generator this size sits on a level concrete plinth outdoors and is wired into your main distribution board through a changeover switch or automatic transfer switch. The work must be done by a registered electrician, who issues a Certificate of Compliance. We supply, deliver, offload and install the complete setup. Our installation guide explains each step.
Part of our Cat range: see all Cat generators for sale, from 33kVA to 500kVA.
See every model and the Cat generator price in South Africa on our Cat generators page.
Common questions
How does the price compare?
See our 50kVA generator price guide and 50kVA generator guide, comparing the Cat with the 44kVA and 55kVA Cummins and the 45kVA Hyundai.
Can it run as a main power source?
It’s rated for standby duty. For continuous prime power, look at a generator with a prime rating, such as the 55kVA Cummins.
How does it compare to the 33kVA Cat?
Both use the Cat C3.3 engine. The 50kVA version is tuned and equipped for more output. See the 33kVA Cat for smaller loads.