50kVA Generator Guide: What It Can Power, Fuel Use and Sizing

A 50kVA generator is one of the most popular sizes for South African businesses. It’s big enough to keep a small supermarket, clinic, school or restaurant fully running through an outage, yet still compact enough to fit behind most commercial buildings. This guide explains what a 50kVA generator can actually power, how much diesel it uses, how to tell whether it’s the right size for you, and what installing one involves.

50kva generator: the 50kVA Cat diesel generator
The 50kVA Cat diesel generator

What can a 50kVA generator power?

At the standard 0.8 power factor, 50kVA is 40kW, roughly 13kW on each of the three phases. Plan around 32kW for comfortable running during an outage, leaving headroom for motors starting.

BusinessWhat a 50kVA typically covers
Small supermarket or convenience storeLighting, tills and card machines, display fridges and freezers, a small cold room and security
Clinic or medical practiceConsulting rooms, aircons, sterilising equipment, vaccine fridges, reception and IT
Primary schoolAdmin block, computer lab, lighting, security and the kitchen fridges
Restaurant (gas cooking)Fridges, freezers, extraction, lighting, coffee machines, dishwasher and aircons
Office of 30 to 40 peopleComputers, printers, lighting, server cupboard and several aircons
FarmThree-phase pumps, a cold room, the workshop and the house
50kVA Cat DE50 GC diesel generator
The 50kVA Cat DE50 GC diesel generator

A worked example: a small supermarket

LoadRunning power
Lighting4kW
Display fridges and freezers12kW
Cold room6kW
Aircons6kW
Tills, card machines, security, Wi-Fi1.5kW
Running totalAbout 29.5kW
Cold room compressor startingA brief extra 8 to 10kW
PeakAbout 38 to 40kW

That’s a good match for a 50kVA, as long as the loads are spread across the three phases and the big compressors don’t all start at once. Add a bakery oven or electric cooking and you’d need to go bigger.

50kVA generator specifications: our Cat DE50 GC

Cat DE50 GC
Rating50kVA / 40kW standby
PhaseThree phase, 400V, 50Hz
EngineCat C3.3, 3 cylinder, 3.3 litre, turbocharged, 1500rpm
AlternatorCat brushless, with AVR
Control panelCat GCCP 1.1
Fuel tank103 litres
Weight1,031kg
Dimensions (L x W x H)2278 x 900 x 1332mm
PriceR120,500 excl. VAT / R138,575 incl. VAT

How much diesel does a 50kVA generator use?

Cat publishes exact figures: 6.0 litres an hour at half load, 8.7 litres at 75% and 11.7 litres at full load. The 103-litre tank lasts about 17 hours at half load and about 12 hours at 75%. For the cost per hour, see our 50kVA generator price guide.

Aerial view of Durban's skyline

Is 50kVA the right size for your business?

Start with the maximum demand on your electricity bill: if your highest month is comfortably under about 40kVA, a 50kVA leaves sensible headroom. Then decide whether the generator must carry everything or only critical loads, which can bring the size down a lot. Our business sizing guide walks through it.

What a 50kVA installation involves

  • A level concrete plinth for a generator of just over a tonne, with space around it for airflow and servicing.
  • A forklift or small crane to offload and place it.
  • An automatic transfer switch, typically 80A or 100A, 4-pole, so it starts and takes over within seconds. See ATS installation.
  • Balanced phases, with your electrician spreading single-phase loads evenly across the three phases.
  • A Certificate of Compliance from a registered electrician.

We handle it all with our own team; see generator installation. Afterwards, regular servicing keeps it ready, and for clinics and other critical sites, a yearly load bank test proves it can carry the full load.

Want us to check whether 50kVA suits your business? Send us your bills or load list. Get a 50kVA quote, or browse our commercial generators.

Frequently asked questions

How many kW is a 50kVA generator?

40kW at 0.8 power factor. Plan around 32kW for comfortable running during an outage.

Can a 50kVA generator run a supermarket?

A small supermarket or convenience store, yes, including fridges and a small cold room. Large supermarkets usually need 100kVA and up.

How big is a 50kVA generator?

Our Cat DE50 GC is 2278 x 900 x 1332mm and weighs 1,031kg.

Is a 50kVA generator single or three phase?

Generators this size are three phase, which suits business premises with a three-phase supply.