Meet the 125kVA Hyundai generator. The DHY125KSE is the most affordable route to 125kVA of three-phase power in our range. It runs a six-cylinder Hyundai engine at 1500rpm, with an AVR alternator, remote start, low-oil shutdown and an ATS connection. Once an automatic transfer switch is fitted, it starts itself when the power fails and shuts down when the grid returns, with no input from you.
It suits office buildings, schools, shopping centres, farms and factories that want solid standby power at a sharp price.
What it will run
It delivers 90kW prime (112kVA) and 100kW standby (125kVA), about 30kW per phase at prime rating. That covers a medium office park, a school campus, a farm with irrigation and cold storage, or a factory with several production lines.
Fuel and running time
Its 245-litre tank gives around 13 hours at half load. For longer outages, an external or bunded tank can be added.
Specifications
| Model | Hyundai DHY125KSE |
| Phase | Three phase, 400V / 230V, 50Hz, 0.8 power factor |
| Prime output | 112kVA / 90kW |
| Standby output | 125kVA / 100kW |
| Engine | Hyundai HY46B155L-D21, 6 cylinder, water cooled |
| Engine speed | 1500rpm |
| Start | Electric, with remote start function |
| Battery | 12V / 60Ah |
| AVR | Yes |
| ATS | ATS connection (switch sold separately) |
| Low oil shutdown | Yes |
| Fuel tank | 245 litres |
| Runtime | About 13 hours at 50% load |
| Noise level | 72dB(A) at 7m |
| Connection | Busbar only |
| Weight | About 1,550 to 1,580kg |
| Dimensions (L x W x H) | About 3200 to 3400 x 1000 to 1050 x 1700 to 1770mm, depending on canopy |
Installation and commissioning
A generator this size needs a level concrete plinth, correctly rated cabling to your main board and an automatic transfer switch sized for your supply, installed by a registered electrician with a Certificate of Compliance. We handle delivery, offloading, installation and commissioning. See our installation guide.
See our 125kVA fuel consumption guide for litres per hour and running costs. Part of our Hyundai range: see all Hyundai generators for sale, single and three phase, from 7.25kVA to 125kVA.
Comparing options around this size? See 110kVA vs 125kVA vs 150kVA: Cummins, Hyundai or Cat.
Common questions
How does it compare to a Cat or Cummins?
It costs considerably less. The 150kVA Cat and 170kVA Cummins bring premium engines and wider dealer support for a higher price.
Does it include an ATS?
The generator is ATS-ready. The transfer switch itself is supplied separately, sized to your building.