Meet the 500kVA Cat generator. This is the biggest generator we sell, built for sites where losing power is not an option: large shopping centres, hospitals, mines, water works, big factories and data centres. The Cat DE500E0 runs Caterpillar’s C15 engine, turbocharged and air-to-air aftercooled, with Cat’s SR500 alternator and the GCCP 1.3 control panel.
It’s also the most searched-for generator on our website, so if you’re researching this size, you’re in good company.
What it will run
It’s rated at 500kVA (400kW) standby and 450kVA (360kW) prime, about 120kW per phase at prime rating. That covers a regional shopping centre, a large hospital, a mine’s surface operations or a full factory.
Built for the big moments
Cat designs these sets to accept 100% of rated load in one step, so the whole building can transfer to the generator at once. The SR500 alternator has strong motor-starting capability, which means you don’t have to oversize the generator just to start large pumps and chillers. Cooling is designed for ambient temperatures up to 50°C.
Sizing it right
For a business, don’t guess. Your electricity bill shows your maximum demand in kVA, the highest load your site actually drew during the month. Size the generator above your highest maximum demand from the last 12 months, plus room for growth and for big motors starting. For critical sites, two 250kVA sets in parallel can be a smarter choice than one 500kVA: if one needs service, the other keeps critical loads running. Send us a few bills and we’ll do the sums with you. Our sizing guide explains the method.
Fuel: the part many buyers underestimate
A generator this size can burn anything from about 25 litres an hour at light load to well over 90 litres an hour at full load. Over a 12-hour outage, that adds up quickly, so plan fuel storage and delivery arrangements before you need them. Large tanks may need approval from your local fire department. We give exact figures for your build on the quote.
Specifications
| Model | Cat DE500E0 |
| Phase | Three phase, 400V, 50Hz |
| Standby rating | 500kVA / 400kW |
| Prime rating | 450kVA / 360kW |
| Engine | Cat C15, 6 cylinder, 15.2 litre, turbocharged, air-to-air aftercooled |
| Engine speed | 1500rpm |
| Alternator | Cat SR500, class H insulation |
| Control panel | Cat GCCP 1.3 |
| Load acceptance | 100% block load in one step |
| Cooling | Radiator, rated for ambient temperatures up to 50°C |
| Fuel tank, canopy and dimensions | Confirmed with your quote for the chosen build |
Installation and commissioning
A generator this size is a proper engineering job: a designed plinth, heavy cabling to the main switchboard, exhaust and cooling airflow planning, crane access and fuel delivery access. Installation must be signed off by a registered electrician with a Certificate of Compliance. We manage the whole project, from site assessment through crane offloading, installation and load testing to handover. See our installation guide.
Part of our Cat range: see all Cat generators for sale, from 33kVA to 500kVA.
Comparing our biggest generators? See 400kVA vs 450kVA vs 500kVA: which is best value?
Common questions
How does the price compare?
See our 500kVA generator price guide and our 500kVA generator guide for what drives the cost, and one 500kVA vs two 250kVA sets.
How long does delivery take?
It depends on the exact build and stock. We confirm lead times with your quote.
What sizes are nearby?
The 450kVA Cummins is the next size down. For larger requirements, ask us about parallel systems.