Meet the 110kVA Cummins generator. The C110D5Q takes the proven Cummins 6BTA5.9 six-cylinder engine and pairs it with a larger Stamford UC274C alternator and a 400-litre base tank. It’s quiet for its size at 68dB(A) at 7 metres, and the electronic governor keeps the power steady for sensitive equipment.
It suits hospitals, shopping centres, office parks, hotels, data rooms and industrial sites with a three-phase supply.
What it will run
It delivers 80kW prime and 88kW standby, about 26kW per phase at prime rating. That covers a shopping centre’s common areas and anchor tenant, a large office building with central aircon, or a factory with multiple production lines.
Fuel and running time
It uses 24.7 litres an hour at full load. The 400-litre base tank gives around 16 hours at full load and much longer at a normal working load.
Specifications
| Model | Cummins C110D5Q |
| Standby power | 110kVA / 88kW |
| Prime power | 100kVA / 80kW |
| Phase | Three phase, 400V, 50Hz |
| Current | 158.4A per phase |
| Engine | Cummins 6BTA5.9-G5, 6 cylinder, electronic governor, 1500rpm |
| Alternator | Stamford UC274C |
| Control panel | Cummins PowerStart 0600 |
| Breaker | 4-pole circuit breaker |
| Base fuel tank | 400 litres |
| Fuel use | 24.7 litres per hour at 100% load |
| Noise level | 68dB(A) at 7m (79dB(A) at 1m) |
| Weight | 1,763kg (dry) |
| Dimensions (L x W x H) | 3100 x 1180 x 1950mm |
| Warranty | 1 year / 500 hours standby, or 1 year unlimited hours prime |
Installation
Generators in this class need a proper plan: a level concrete plinth, room for airflow and service access, a correctly sized cable run to the main board, and an automatic transfer switch rated for your supply. The installation must be done by a registered electrician, who issues a Certificate of Compliance. We handle delivery, crane offloading, installation and commissioning. See our installation guide for more.
Part of our Cummins range: see all Cummins generators for sale, from 17kVA to 450kVA.
Comparing options around this size? See 110kVA vs 125kVA vs 150kVA: Cummins, Hyundai or Cat.
Common questions
Is 110kVA right for my building?
Send us your electricity bill or a load list and we’ll size it properly. Our sizing guide explains how.
What sizes are nearby?
The 90kVA Cummins below it, and the 125kVA Hyundai and 150kVA Cat above. See the full industrial range.