125kVA Generator Fuel Consumption: Litres Per Hour and Running Costs

125kVA generator fuel consumption, in litres per hour: plan on roughly 12 to 14 litres an hour at half load and about 25 to 27 litres at full prime load for a modern six-cylinder 125kVA set. Those figures, and what they cost you in rand, are what this guide is about. We’ll use our Hyundai DHY125KSE 125kVA generator as the example, and compare it with the published figures of the generators either side of it.

125kva generator fuel consumption: the 125kVA Hyundai diesel generator
The 125kVA Hyundai diesel generator

125kVA generator fuel consumption per hour in litres

Our Hyundai is rated 90kW prime and 100kW standby. These planning figures are based on its rating and on the published consumption of comparable six-cylinder sets:

LoadPower (approx.)Diesel per hour (planning figure)Hours on the 245-litre tank
25%About 22kW7 to 9 litresAbout 27 to 35
50%About 45kW12 to 14 litresAbout 18 to 20
75%About 67kW18 to 20 litresAbout 12 to 13
100% (prime)90kW25 to 27 litresAbout 9 to 10

A note on Hyundai’s own figure: Hyundai doesn’t publish a full fuel table for this model. It quotes about 13 hours at half load on the 245-litre tank, which works out to roughly 19 litres an hour. That’s higher than comparable sets use in practice, so treat it as a conservative, worst-case figure for planning fuel deliveries. We confirm the figures for your build on the quote.

125kVA Hyundai DHY125KSE diesel generator
The 125kVA Hyundai DHY125KSE diesel generator

How it compares with generators that publish their figures

GeneratorRatingPublished diesel use
90kVA Cummins66kW prime21.2 L/h at full load
110kVA Cummins80kW prime24.7 L/h at full load
125kVA Hyundai90kW primeAbout 25 to 27 L/h at full prime load (planning figure)
150kVA Cat120kW standby17.4 L/h at 50%, 24.8 at 75%, 33.2 at full load

For a full comparison of these three, see 110kVA vs 125kVA vs 150kVA. The pattern is clear: large diesel generators burn roughly a quarter to a third of a litre for every kWh they produce, and fuel follows the load, not the size of the machine.

What it costs to run a 125kVA generator

At R25 a litre (check today’s diesel price):

LoadCost per hour8-hour outage
50%About R300 to R350About R2,400 to R2,800
75%About R450 to R500About R3,600 to R4,000
100% (prime)About R625 to R675About R5,000 to R5,400

A monthly example: a supermarket with two four-hour outages a week, running at about half load, uses roughly 13 litres an hour for 8 hours a week. That’s about 450 litres a month, or around R11,000 at R25 a litre.

125kVA Hyundai DHY125KSE generator canopy and control panel
The 125kVA Hyundai DHY125KSE generator canopy and control panel

How to use less diesel

  • Size it to your real load. A generator running very lightly for long periods wastes fuel and builds up soot. See our business sizing guide.
  • Back up only what matters. Keep non-essential loads off the generator board.
  • Keep it serviced. Clean filters, injectors and fresh oil keep consumption down; see generator servicing.
  • Keep the diesel clean. Water and sludge in the tank cost you efficiency; see fuel management.
  • Measure it. Remote monitoring shows fuel level and running hours, so you see exactly what you use.

The 125kVA Hyundai at a glance

Six-cylinder, water-cooled engine at 1500rpm, AVR, remote start, an ATS connection, a 245-litre tank and 72dB(A) at 7 metres. It costs R229,900 excl. VAT / R264,385 incl. VAT, and is ordered in, with the lead time confirmed on your quote. Browse more Hyundai generators or our industrial range, or ask for a 125kVA quote.

Planning for a long outage? See how long a diesel generator can run continuously.

Frequently asked questions

How many litres of diesel does a 125kVA generator use per hour?

Roughly 12 to 14 litres at half load and 25 to 27 litres at full prime load, for a modern six-cylinder set.

How long will a 125kVA generator run on a full tank?

Our Hyundai’s 245-litre tank lasts about 9 to 10 hours at full prime load, and longer at lower loads.

What does a 125kVA generator cost to run per hour?

At R25 a litre, roughly R300 to R350 an hour at half load and about R625 to R675 at full prime load.

Does a bigger generator use more fuel?

Not for the same load. Fuel follows the load you put on the generator, not its size.