High call volumes. We are receiving a lot of calls and enquiries right now. For the fastest reply, email us, request a quote online or message us on WhatsApp.

Bloemfontein based. Delivery and installation across South Africa.

40kVA Generator: Cummins 44kVA vs Hyundai 45kVA Compared

Looking for a 40kVA generator? We sell two, and both deliver exactly 40kVA (32kW) on their prime rating: the Cummins C44D5e, sold as a 44kVA, and the Hyundai DHY45KSE, sold as a 45kVA. The bigger names come from their standby ratings. Same continuous power, but different prices, fuel use and running times, so the right choice depends on how many hours your generator will actually run.

40kva generator: the 45kVA Hyundai diesel generator
The 45kVA Hyundai diesel generator

40kVA generator comparison: Cummins 44kVA vs Hyundai 45kVA

Cummins 44kVAHyundai 45kVA
ModelC44D5eDHY45KSE
Prime (continuous)40kVA / 32kW40kVA / 32kW
Standby44kVA / 35kW45kVA / 33 to 36kW
EngineCummins 4BTAA3.3, turbochargedHyundai 4 cylinder, 4.1 litre
AlternatorStamfordHyundai, AVR
Fuel tank180 litres93 litres
Diesel at full load10.2 L/h12.8 L/h
Running time at full loadAbout 18 hoursAbout 7 hours
Noise76dB(A) at 1m65dB(A) at 7m
Current per phase63.3AAbout 63A
Warranty noteUnlimited hours on prime in year oneAs per manufacturer
PriceR112,800 excl. VAT / R129,720 incl. VATR88,900 excl. VAT / R102,235 incl. VAT

Both are three phase and in stock. Prices exclude installation and the transfer switch, typically a 63A or 80A 4-pole unit for this size.

The Hyundai 45kVA: less to buy, quieter

45kVA Hyundai DHY45KSE diesel generator
The 45kVA Hyundai DHY45KSE diesel generator

The Hyundai costs about R23,900 less, and at 65dB(A) at 7 metres it’s noticeably quieter. It has AVR, an ATS port and 230V sockets as well as a busbar connection. The trade-off is its 93-litre tank, which lasts about 7 hours at full load. For backup during outages, that’s usually plenty. See our Hyundai generators.

The Cummins 44kVA: cheaper to run, runs longer

44kVA Cummins C44D5e diesel generator
The 44kVA Cummins C44D5e diesel generator

The Cummins uses 10.2 litres an hour at full load, against 12.8 for the Hyundai, and its 180-litre tank lasts about 18 hours. Add a Stamford alternator and a warranty allowing unlimited prime running hours in year one, and it’s built for sites that run long hours. See our Cummins generators.

When does the Cummins pay for itself?

At full load, the Cummins saves about 2.6 litres an hour. At R25 a litre (check today’s diesel price), that’s about R65 an hour. So its extra purchase price is paid back after roughly 370 hours at full load, and longer at lower loads.

  • A few outages a month? You may run 100 to 200 hours a year. The Hyundai is the better buy.
  • Long daily running, or off the grid? You could pass 370 hours in a few months. The Cummins wins over time.

What a 40kVA generator runs

32kW continuous covers a busy shop or hardware store, a restaurant with gas cooking, a clinic, an office of 30 to 40 people, or a farm with three-phase pumps and a cold room. For a worked example at this size, see our 50kVA generator guide, and compare prices across the class in our 50kVA price guide and 30kVA price guide.

Get a quote, including installation.

For more on the Hyundai on its own, see our 45kVA generator guide.

Frequently asked questions

How much is a 40kVA generator?

Our two 40kVA-prime generators are the Hyundai 45kVA at R88,900 excl. VAT / R102,235 incl. VAT and the Cummins 44kVA at R112,800 excl. VAT / R129,720 incl. VAT, before installation.

How much diesel does a 40kVA generator use?

At full load, 10.2 litres an hour on the Cummins and 12.8 on the Hyundai. At half load, the Hyundai uses about 7.2 litres an hour.

Why is a 40kVA generator sold as 44kVA or 45kVA?

The bigger number is the standby rating. Both deliver 40kVA continuously on their prime rating.

Which is quieter?

The Hyundai, at 65dB(A) at 7 metres.