Generator for a Borehole Pump: What Size Do You Need?
What size generator for a borehole pump? Much bigger than the pump’s rating suggests. A borehole pump’s motor pulls three to seven times its running power for the second or two it takes to start, especially a deep submersible pump starting against a full column of water. Size the generator for the running power alone, and the pump won’t start, or it will trip the generator. Here’s how to get it right.

Generator for a borehole pump: quick sizing guide
| Pump | Supply | Minimum generator (pump only) | Our example |
|---|---|---|---|
| 0.37 to 0.55kW | Single phase | 5 to 6kVA | 7.25kVA Hyundai |
| 0.75kW | Single phase | 6 to 7kVA | 7.25kVA Hyundai |
| 1.1kW | Single phase | 7 to 8kVA | 10kVA Hyundai |
| 1.5kW | Single phase | 8 to 10kVA | 10kVA Hyundai |
| 2.2kW | Single phase | 10 to 12.5kVA | 12.5kVA Hyundai |
| 4kW | Three phase | 12 to 15kVA | 15kVA Himoinsa |
| 5.5kW | Three phase | 15 to 20kVA | 20kVA Himoinsa |
| 7.5kW | Three phase | 20 to 25kVA | 22kVA Hyundai |
These are for the pump on its own, started direct. If the generator also runs the house, add the house load on top. Check the motor’s nameplate (kW, voltage and phase) before buying; the exact figure depends on the pump, its depth and how it starts. The sizes are a guide, and we confirm yours for free.
Why borehole pumps need such a big generator
An electric motor draws a large surge of current while it gets up to speed, called the starting or inrush current. A submersible pump deep in a borehole also has to push a full column of water from a standstill, which makes the surge worse. Generators handle short surges, but only up to a point, so the generator has to be sized for the start, not the run.

How to use a smaller generator
- Fit a soft starter or a variable speed drive on the pump. Both cut the starting surge dramatically, sometimes letting you drop a full size.
- Start the pump first, before other big loads like aircons or the geyser.
- Use a pressure tank, so the pump starts less often.
- On farms, consider three phase. Three-phase pumps start more easily than single-phase pumps of the same size; see 3 phase generators.
Borehole pump and the house together
When you choose a generator for a borehole pump at home, remember that most homes want the borehole, fridges, lights and Wi-Fi running together. A typical family home with a 0.75 to 1.1kW borehole pump is comfortable on a 10kVA to 12.5kVA generator, with the geyser off. See how many kVA to run a house and our generator sizing guide.
Send us the pump’s nameplate details and what else must run, and we’ll size the right generator for a borehole pump like yours, for free. Get a quote.
Sizing for the whole farm, not just the pump? Read our farm generator guide.
Frequently asked questions
What size generator for a 1.5kW borehole pump?
About 8 to 10kVA for the pump alone. Our 10kVA Hyundai is a common choice.
Can a 5kVA generator run a borehole pump?
Only a small one, up to about 0.55kW, started on its own.
Why does my generator trip when the pump starts?
The pump’s starting surge is too big for the generator. A larger generator or a soft starter fixes it.
Do I need a three-phase generator for my borehole?
Only if the pump is three phase. Most household borehole pumps are single phase.